Loading...
PRODUCT  >>  ON - Line  >> Vanguard Chain II    

   VCRII - Vanguard Chain II

  • Pure Sine Wave Output with Power Factor 1.0

  • Parallel capability, maximum 4 units (optional)

  • Diagram LCD for better status indication

  • High efficiency with complicated load

  • Overload, Surge, Short Circuit Protection

  • VCR II - 6000 / 10000VA

  •  UPS
    Model
    VCRII-6000
    VCRII-10000
    Capacity(VA)
    6000 VA
    10000 VA
    Capacity(Watts)
    6000 W
    10000 W
    Form
    Rack and Tower Type
    Phase
    Single Phase
    Energy Saving
    ECO Mode Efficiency: 98%
    Line mode with battery full charged: 94.6%@100% load, 95%@60% load

     PHASE
    Phase
    Single phase in,single phase out
    Transfer Voltage Range
    200VAC/208VAC/220VAC/230VAC/240VAC
    Line low transfer
    110VAC
    Line low recovery
    121VAC
    Line high transfer
    288VAC
    Line high recovery
    281VAC

     INPUT
    Voltage
    110VAC~288VAC
    Voltage Range
    100% load@>176VAC
    90% load@>154VAC
    75% load@>132VAC
    50% load@>110VAC
    Input Current Rating (full charging)
    30A / 220V
    49A / 220V
    Input Frequency Range
    40~70Hz
    Input current distortion
    <4%
    Input Power Factor
    >=0.99
    Cold Start
    Yes

     OUTPUT
    Rated Power Factor
    1.0
    Waveform
    Pure Sine Wave
    Voltage
    220VAC/230VAC/240VAC ± 1 %, 200VAC/208VAC ± 1 %
    Frequency
    50 / 60 Hz
    Synchronization range
    ±5Hz default, settable
    Transfer Time
    0 ms
    Harmonic Distortion
    ≤ 1% THD, linear load ≤ 5% THD, non linear load
    Crest Factor
    3 : 1
    EPO Function
    Standard

     PROTECTION
    Overload Inverter
    105% to 110% : Transfer to bypass after 10 mins
    111% to 125% : Transfer to bypass after 1 mins
    126% to 150%: Transfer to bypass after 30s
    Bypass Mode
    less than 125%: long time running
    126% to 130% :Shutdown in 5 mins
    131% to 150% :Shutdown in 1 mins
    >150% :Shutdown in 200 ms

     BATTERY
    Model
    VCRII-6000
    VCRII-10000
    Type
    12V 7Ah
    12V 9Ah
    Quantity
    16PCS default
    DC Voltage
    192VDC default
    Back-up Time
    3mins @5kW
    2mins @8kW
    Typical Recharge Time
    8h recharge to 90%

     CHARGER
    Charging current (max)
    1A
    Float Charging Voltage
    2.25V/cell default, setttable via software
    Boost Charging Voltage
    2.25V/cell default, setttable via software
    Charging time
    8h recharge to 90%
    Leakage current
    <3mA

     MANAGEMENT & COMMUNICATION
    Indicator
    LED+LCD
    Communication Port
    Standard: RS 232
    Option: USB B type, SNMP card, RS 485, DB9 port, dry contact,10A charger
    (charger current settable: 1-10A)

     PHYSICAL
    Dimensions(WxDxH)(mm)
    440 x 660 x 172
    Weights(Kgs)
    58
    62

     ENVIRONMENT
    Operating Humidity
    0-95 % RH at 0-40°C (Non-condensing)
    Audible Noise
    <58dB (1m away)
    * While 208V output, capacity will derated to 90%

    * Specifications are subject to change without further notice

    * Specifications are for reference, actual information should be based on real product

     Document
     Catalog    



    VANGUARD CHAIN II On-Line UPS outputs pure sine wave with Power Factor 1.0. VCR II UPS equipped with LCD and LED display, users can acquire UPS information instantly from the front panel. VCR II intelligent fan system automatically adjusts fan speed base on power load, maintains optimal temperature control and noise emission. VCR II Intelligent Charging Management improve charging efficiency and effectively extend the battery life. .VCR II series have 3-level technology, compatible with complicated load. VCR II are designed as the safe guard of high-class computers, telecommunication equipment and servers.
     Feedback
     Message Link   
     EMail Link   
     Phone Tel : 886-2-2225-8552